OD MODEL
4A6H4060G1

ID MODEL
4TXCC009DS3

NOM CFM
1580

ARI REF #
10513116

Published Date: 12/07/2022

COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES

OD AMB
ID WBTOT CAP72757880KW
85
5954.0042.1047.048.9048.604.17
6356.6034.8039.644.4047.704.21
6760.5027.9032.737.5040.704.25
7165.6021.3026.130.9034.104.29
95
5951.6041.0045.848.9048.604.75
6354.1033.7038.643.4046.604.79
6757.8026.8031.736.5039.704.84
7162.7020.2025.029.8033.104.88
105
5949.2039.9044.748.9048.605.32
6351.6032.7037.542.3045.505.37
6755.1025.8030.635.4038.605.42
7159.8019.2024.028.8032.005.47
115
5946.8038.8043.646.8046.805.89
6349.1031.6036.441.2044.405.95
6752.4024.7029.634.4037.606.01
7156.9018.1023.027.8031.006.07

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW RATE, CFM.CAPACITY MULTIPLIERTOTAL POWER MULTIPLIER
13750.980.99
17751.021.01

ARI RATING FOR COOLING

CFMCAPACITY (A) TESTSEEREER
14005650014.0011.50

A.R.I. Standard Capacity Rating Conditions

A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.

 

 

 

 

OD MODEL
4A6H4060G1

ID MODEL
4TXCC009DS3

NOM CFM
2000

ARI REF #
10513116

Published Date: 12/07/2022

HEATING PERFORMANCE AT INDOOR DRY BULB TEMPERATURE

 TOTAL CAPACITY MBH.TOTAL POWER IN KILOWATTS
OD AMB6070758060707580
229.8029.3029.0028.704.144.354.464.57
732.8032.2031.9031.604.164.374.484.59
1235.8035.1034.8034.504.174.394.504.61
1738.8038.1037.7037.404.194.414.524.63
2240.4039.7039.3038.904.194.414.524.63
2742.0041.2040.8040.404.184.404.514.62
3243.6042.8042.4042.004.184.404.514.62
3746.6045.7045.3044.904.204.424.534.64
4251.7050.7050.2049.704.254.484.594.70
4756.7055.7055.1054.604.314.534.654.76
5259.7058.6058.0057.504.334.554.674.78
5762.7061.5060.9060.304.354.574.694.80
6265.7064.5063.8063.204.374.604.714.82
6768.7067.4066.7066.104.384.624.734.85
7271.7070.3069.6069.004.404.644.754.87

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW RATE, CFM.CAPACITY MULTIPLIERTOTAL POWER MULTIPLIER
17500.990.98
22501.011.03

ARI RATING FOR HEATING

CFMCAPACITY 47COP 47CAPACITY 17COP 17HSPF
1400535003.70366002.608.20

A.R.I. Standard Capacity Rating Conditions

A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.